Main page
»
Products
»
GEFRAN
»
Automation
»
displays - limit monitor
»
GEFRAN 40T 72 CONFIGURABLE INDICATOR
GEFRAN 40T 72 CONFIGURABLE INDICATOR
Main features
• Faceplate configurable input
• Protected by a personal code
• Configurable by a serial link
• Transmitter power supply incorporated
• Custom thermocouple linearisation
available
• Internal linearisation for engineering
units
• Labels provided for the more common
physical units
• Sampling time and trip intervention
programmable between 15 and
120msec with resolution between
2000 and 8000 steps
• Retransmission of the measured
variable signal
• 3 trip points, completely configurable
from the faceplate
Main applications
• Thermostat
• Humidity switch
• Mould cooling units
• Industrial refrigerators
• Air conditioning
• Food processing equipment
Order-no.: F182
Manufacturer: GEFRAN
SAGATRON-no.: F182
• Faceplate configurable input
• Protected by a personal code
• Configurable by a serial link
• Transmitter power supply incorporated
• Custom thermocouple linearisation
available
• Internal linearisation for engineering
units
• Labels provided for the more common
physical units
• Sampling time and trip intervention
programmable between 15 and
120msec with resolution between
2000 and 8000 steps
• Retransmission of the measured
variable signal
• 3 trip points, completely configurable
from the faceplate
Main applications
• Thermostat
• Humidity switch
• Mould cooling units
• Industrial refrigerators
• Air conditioning
• Food processing equipment
Order-no.: F182
Manufacturer: GEFRAN
SAGATRON-no.: F182
INPUTS
Accuracy 0,2% f.s. ±1digit.
Sampling time 120msec for temperature
sensors, configurable for linear inputs
down to a minimum of 15msec with
reduction of the resolution to 2000 steps.
Configurable decimal point position for
linear inputs, for TC, RTD, PTC and NTC
inputs, only one decimal digit is allowed
in the maximum display range of
-199.9 to 999.9 (4 digit display),
-99.9 to 99.9 (3 digit display with sign),
-9.9 to 9.9 (2 digit display with sign) with
indication of open circuit thermocouple or
RTD, PTC or NTC in open or short circuit,
indication of over- and under-range for
linear inputs.
TC - Thermocouple
Automatic cold junction compensation
(4 digit)
J 0 to 1000°C / 32 to 1832°F
K 0 to 1300°C / 32 to 2372°F
R 0 to 1750°C / 32 to 3182°F
S 0 to 1750°C / 32 to 3182°F
T -200 to 400°C / -328 to 752°F
B 44 to 1800°C / 111 to 3272°F
E -100 to 750°C / -148 to 1382°F
N 0 to 1300°C / 32 to 2372°F
L-GOST 0 to 600°C / 32 to 1112°F
U -200 to 400°C / -328 to 752°F
G 0 to 2300°C / 32 to 4172°F
D 0 to 2300°C / 32 to 4172°F
C 0 to 2300°C / 32 to 4172°F
custom -1999 to 9999
TC - Thermocouple
(3 digit + sign)
J 0 to 999°C / 32 to 999°F
K 0 to 999°C / 32 to 999°F
R 0 to 999°C / 32 to 999°F
S 0 to 999°C / 32 to 999°F
T -200 to 400°C / -328 to 752°F
B not available
E -100 to 750°C / -148 to 999°F
N 0 to 999°C / 32 to 999°F
L-GOST 0 to 600°C / 32 to 999°F
U -200 to 400°C / -328 to 752°F
G 0 to 999°C / 32 to 999°F
D 0 to 999°C / 32 to 999°F
C 0 to 999°C / 32 to 999°F
custom -999 to 999
(2 digit + sign)
J 0 to 99°C / 32 to 99°F
K 0 to 99°C / 32 to 99°F
R 0 to 99°C / 32 to 99°F
S 0 to 99°C / 32 to 99°F
T -99 to 99°C / -99 to 99°F
B not available
E not available
N not available
L-GOST 0 to 99°C / 32 to 99°F
U -99 to 99°C / -99 to 99°F
G not available
D not available
C not available
custom -99 to 99
RTD (2 or 3 wire)
(4 digit)
PT100 -200 to 600°C / -328 to 1112°F
JPT100 -200 to 600°C / -328 to 1112°F
(3 digit + sign)
PT100 -200 to 600°C / -328 to 999°F
JPT100 -200 to 600°C / -328 to 999°F
(2 digit + sign)
PT100 -99 to 99°C / -99 to 99°F
JPT100 -99 to 99°C / -99 to 99°F
PTC
990Ω, 25°C
(4 digit and 3 digit + sign)
-55 to 120°C / -67 to 248°F
(2 digit + sign)
-55 to 99°C / -67 to 99°F
NTC
1KΩ, 25°C
(4 digit and 3 digit + sign)
-10 to 70°C / 14 to 158°F
(2 digit + sign)
-10 to 70°C / 14 to 99°F
DC - Linear
With scale configurable within the limits:
-1999 to 9999 (4 digit),
-999 to 999 (3 digit + sign)
-99 to 99 (2 digit + sign)
0 to 60mV / 12 to 60mV
0 to 10V / 2 to 10V
0 to 5V / 1 to 5V
0 to 1V / 0,2 to 1V
0 to 20mA / 4 to 20mA
Input impedance for voltage signals
Ri > 500KΩ, for current signals Ri = 50Ω.
32-segment configurable linearisation can
be used.
Potentiometer
Supply 1V >100Ω
Digital input
Ri = 5,6KΩ (24V, 4mA) isolated to 1500V
Function is configurable as alarm or
memory reset, hold, flash zero, display of
the peak value (max., min. or peak to
peak).
OUTPUTS
Relay
with NO (NC) contacts rated at 5A, 250V
at cosϕ = 1.
Logic (only for Out1 and Out2)
Output, type D 11Vdc, Rout = 220Ω
(6V/20mA).
Triac (for Out1, disabled Out2)
24 to 240Vac ±10%, 2A max
Snubberless, I2t = 128A2sec
A maximum of three trip points can be set
as absolute, deviation or symmetrical
deviation alarms.
The hysteresis of each alarm is
configurable individually.
Alarm masking with exclusion on power
up, with memory, delay and minimum
intervention time.
The trip point may be set at any point on
the scale.
Analogue retransmission
4 to 20mA on max. 60Ω
POWER SUPPLY
11...27Vdc, 18...27Vac ± 10%
50/60Hz, max. 4,5VA
TRANSMITTER POWER SUPPLY
2 wire, 18Vdc ±10%, max. 50mA
1,2Vdc for potentiometer >100Ω
(non isolated from sensor input)
AMBIENT CONDITIONS
Working temperature range: 0 to 50°C
Storage temperature range: -20 to 70°C
Humidity: 20 to 85%Ur non-condensing
WEIGHT
110g. in the complete version
Accuracy 0,2% f.s. ±1digit.
Sampling time 120msec for temperature
sensors, configurable for linear inputs
down to a minimum of 15msec with
reduction of the resolution to 2000 steps.
Configurable decimal point position for
linear inputs, for TC, RTD, PTC and NTC
inputs, only one decimal digit is allowed
in the maximum display range of
-199.9 to 999.9 (4 digit display),
-99.9 to 99.9 (3 digit display with sign),
-9.9 to 9.9 (2 digit display with sign) with
indication of open circuit thermocouple or
RTD, PTC or NTC in open or short circuit,
indication of over- and under-range for
linear inputs.
TC - Thermocouple
Automatic cold junction compensation
(4 digit)
J 0 to 1000°C / 32 to 1832°F
K 0 to 1300°C / 32 to 2372°F
R 0 to 1750°C / 32 to 3182°F
S 0 to 1750°C / 32 to 3182°F
T -200 to 400°C / -328 to 752°F
B 44 to 1800°C / 111 to 3272°F
E -100 to 750°C / -148 to 1382°F
N 0 to 1300°C / 32 to 2372°F
L-GOST 0 to 600°C / 32 to 1112°F
U -200 to 400°C / -328 to 752°F
G 0 to 2300°C / 32 to 4172°F
D 0 to 2300°C / 32 to 4172°F
C 0 to 2300°C / 32 to 4172°F
custom -1999 to 9999
TC - Thermocouple
(3 digit + sign)
J 0 to 999°C / 32 to 999°F
K 0 to 999°C / 32 to 999°F
R 0 to 999°C / 32 to 999°F
S 0 to 999°C / 32 to 999°F
T -200 to 400°C / -328 to 752°F
B not available
E -100 to 750°C / -148 to 999°F
N 0 to 999°C / 32 to 999°F
L-GOST 0 to 600°C / 32 to 999°F
U -200 to 400°C / -328 to 752°F
G 0 to 999°C / 32 to 999°F
D 0 to 999°C / 32 to 999°F
C 0 to 999°C / 32 to 999°F
custom -999 to 999
(2 digit + sign)
J 0 to 99°C / 32 to 99°F
K 0 to 99°C / 32 to 99°F
R 0 to 99°C / 32 to 99°F
S 0 to 99°C / 32 to 99°F
T -99 to 99°C / -99 to 99°F
B not available
E not available
N not available
L-GOST 0 to 99°C / 32 to 99°F
U -99 to 99°C / -99 to 99°F
G not available
D not available
C not available
custom -99 to 99
RTD (2 or 3 wire)
(4 digit)
PT100 -200 to 600°C / -328 to 1112°F
JPT100 -200 to 600°C / -328 to 1112°F
(3 digit + sign)
PT100 -200 to 600°C / -328 to 999°F
JPT100 -200 to 600°C / -328 to 999°F
(2 digit + sign)
PT100 -99 to 99°C / -99 to 99°F
JPT100 -99 to 99°C / -99 to 99°F
PTC
990Ω, 25°C
(4 digit and 3 digit + sign)
-55 to 120°C / -67 to 248°F
(2 digit + sign)
-55 to 99°C / -67 to 99°F
NTC
1KΩ, 25°C
(4 digit and 3 digit + sign)
-10 to 70°C / 14 to 158°F
(2 digit + sign)
-10 to 70°C / 14 to 99°F
DC - Linear
With scale configurable within the limits:
-1999 to 9999 (4 digit),
-999 to 999 (3 digit + sign)
-99 to 99 (2 digit + sign)
0 to 60mV / 12 to 60mV
0 to 10V / 2 to 10V
0 to 5V / 1 to 5V
0 to 1V / 0,2 to 1V
0 to 20mA / 4 to 20mA
Input impedance for voltage signals
Ri > 500KΩ, for current signals Ri = 50Ω.
32-segment configurable linearisation can
be used.
Potentiometer
Supply 1V >100Ω
Digital input
Ri = 5,6KΩ (24V, 4mA) isolated to 1500V
Function is configurable as alarm or
memory reset, hold, flash zero, display of
the peak value (max., min. or peak to
peak).
OUTPUTS
Relay
with NO (NC) contacts rated at 5A, 250V
at cosϕ = 1.
Logic (only for Out1 and Out2)
Output, type D 11Vdc, Rout = 220Ω
(6V/20mA).
Triac (for Out1, disabled Out2)
24 to 240Vac ±10%, 2A max
Snubberless, I2t = 128A2sec
A maximum of three trip points can be set
as absolute, deviation or symmetrical
deviation alarms.
The hysteresis of each alarm is
configurable individually.
Alarm masking with exclusion on power
up, with memory, delay and minimum
intervention time.
The trip point may be set at any point on
the scale.
Analogue retransmission
4 to 20mA on max. 60Ω
POWER SUPPLY
11...27Vdc, 18...27Vac ± 10%
50/60Hz, max. 4,5VA
TRANSMITTER POWER SUPPLY
2 wire, 18Vdc ±10%, max. 50mA
1,2Vdc for potentiometer >100Ω
(non isolated from sensor input)
AMBIENT CONDITIONS
Working temperature range: 0 to 50°C
Storage temperature range: -20 to 70°C
Humidity: 20 to 85%Ur non-condensing
WEIGHT
110g. in the complete version
Input | Output | Special functions | Power Supply | Typ | Code |
Thermocouple, Pt100, standard signals | 2 Relay | --- | 11..27Vdc /18..27Vac | 40T-72-3-00-RR-00-9 | F182 |
Thermocouple, Pt100, standard signals | 2 Relay + Analog | --- | 11..27Vdc /18..27Vac | 40T-72-3-00-RR-02-9 | F183 |
Thermocouple, Pt100, standard signals | 3 Relay | --- | 11..27Vdc /18..27Vac | 40T-72-3-00-RR-R0-9 | F184 |
Thermocouple, Pt100, standard signals | 2 Relay | 4 digits | 11..27Vdc /18..27Vac | 40T-72-4-00-RR-00-9 | F185 |
Thermocouple, Pt100, standard signals | 2 Relay + Analog | 4 digits | 11..27Vdc /18..27Vac | 40T-72-4-00-RR-02-9 | F915 |
Thermocouple, Pt100, standard signals | 3 Relay | 4 digits | 11..27Vdc /18..27Vac | 40T-72-4-00-RR-R0-9 | F916 |
Thermocouple, Pt100, standard signals, Potentiometer | 2 Relay | 4 digits + transmitter supply 1,25 Vdc | 11..27Vdc /18..27Vac | 40T-72-4-01-RR-00-9 | F186 |
Thermocouple, Pt100, standard signals, Potentiometer | 3 Relay | 4 digits + transmitter supply 1,25 Vdc | 11..27Vdc /18..27Vac | 40T-72-4-01-RR-R0-9 | F41.099 |
Thermocouple, Pt100, standard signals, Potentiometer | 2 Relay + Analog | 4 digits + transmitter supply 1,25 Vdc | 11..27Vdc /18..27Vac | 40T-72-4-01-RR-02-9 | F26.040 |
Thermocouple, Pt100, standard signals | 2 Relay | 4 digits + transmitter supply 24 Vdc | 11..27Vdc /18..27Vac | 40T-72-4-24-RR-00-9 | F917 |
Thermocouple, Pt100, standard signals | 2 Relay + Analog | 4 digits + transmitter supply 24 Vdc | 11..27Vdc /18..27Vac | 40T-72-4-24-RR-02-9 | F918 |
Thermocouple, Pt100, standard signals | 3 Relay | 4 digits + transmitter supply 24 Vdc | 11..27Vdc /18..27Vac | 40T-72-4-24-RR-R0-9 | F919 |
Unfortunately there are no review yet. Be the first who rate this product.