General features
Category of use: AC51, AC53a
Nominal voltage (Ue):
400Vac (max. range 24...440Vac) (TRIAC)
480Vac (max. range 24..530Vac) (SCR)
600Vac (max. range 24..660Vac) (SCR)
Nominal frequency: 50/60Hz
Peak voltage:
<800Vp for models with Ue=400Vac
<1200Vp for models with Ue=480Vac,
Ue=600Vac
Uninterrupted nominal service.
Critical dV/dt OFF-state:
500V/μs for models with Ue=400Vac
1000V/μs for models with Ue=480Vac,
Ue=600Vac
Switching voltage for zero: < 20V
Activation time: ≤1/2 cycle
Deactivation time: ≤1/2 cycle
Potential drop at rated current: ≤ 1,4Vrms
IP20 protection
Weight:
GTZ 25:1100g
GTZ 40, 55:1350g
Control inputs
DC INPUT (Type “D”):
Voltage of command circuit (Uc): 5..32Vdc
Activation voltage: >4.5Vdc
Deactivation voltage: <3Vdc
Max. input: 18mA@5Vdc- 22mA@32Vdc
Max. reverse voltage: 36Vdc
AC INPUT (Type “A”):
Control voltage: 20...260Vac/Vdc
Activation voltage: > 15Vac/Vdc
Deactivation voltage: < 6Vac/Vdc
Current draw:
<= 8 mAac/dc@260Vac/Vdc
Additional fuse (3A max) shall be installed
on the control input circuit.
Outputs
GTZ 25/...
Nominal current (Imax):
AC51: 3x25 A
AC53a: 3x5 A
GTZ 40/...
Nominal current (Imax):
AC51: 3x40 A
AC53a: 3x8 A
GTZ 55/...
Nominal current (Imax):
AC51: 3x55 A
AC53a: 3x15 A
Insulation
Nominal insulation voltage input/output:
2.5KV ac for models with Ue=400Vac
4KV ac for models with Ue=480Vac,
Ue=600Vac
Nominal impulse withstand voltage
(Uimp): 2500Vac
Ambient conditions
• Working temperature: -20°C...80°C
• Max. relative humidity: 50% to 40°C
• Max. installation altitude: 2000 slm
• Pollution level : 2
• Storage temperature: -20...85°C
• Class: A (industrial device)
• Suitable for use in pollution degree 2
environmental
Thermal protection
SCR temperature is constantly monitored
inside the device.
If the maximum temperature limit is
exceeded (T=110°C), current to the load
is interrupted and the yellow signal LED
lights up.
Options
Option -1
(Thermal protection alarm output).
The alarm output option activates closing
of an isolated contact (max 32VAC/VDC,
150mA, conducting resistance <=15
ohm) when it detects the following fault
condition: control signal active but SCR/
heatsink is in overtemperature (GTZ thermal
protection)
Option -2
(Thermal protection alarm output and interrupted
load).
Only for GTZ with Type “A” input.
The alarm output option activates closing
of an isolated contact (max 32VAC/VDC,
150mA, conducting resistance <=15 ohm)
when it detects the following fault conditions:
- Control signal active but no current in at
least one three-phase branch (interrupted
load)
- Control signal active but no power line
voltage (no line)
- Control signal active but SCR / heatsink
is in overtemperature (GTZ thermal protection).
Maximum delay in tripping of load
interrupt
alarm < 400ms.
Maximum length of wires between GS and
load for correct operation of load diagnostics
< 25m
Power supply
Fan supply (only for models GTZ 40/55A):
230Vac 14W (VEN90)
115Vac 14W (VEN91)
24Vdc 4W (VEN92)
TECHNICAL DATA OF THE MAIN CIRCUIT